Loading EveryPlace content…
Loading EveryPlace content…

State license
Active
WA DSHS
Size & payment
92 residents
Confirm pricing & payment
Strong public signals
Rated 4.6/5 across 11 public Google reviews. Visit in person to confirm daily care and pricing.
Families praise: Caring and compassionate staff
Worth asking: Inconsistent food quality (mentioned by 2 reviewers)
| Monthly cost | Not published | Ask for the full monthly cost, including care fees and one-time charges. |
|---|---|---|
| Payment options | Ask directly | Payment details are not confirmed in our records. Ask about private pay, long-term care insurance, veterans benefits, and Medicaid waivers. |
| Size & availability | 92 residents | We don't publish live openings. Ask about current availability, waitlist length, and move-in timing. |
| Care & support | Assisted living | Usually offers housing and help with everyday tasks, such as bathing and dressing. What to confirm about care levelsThis describes the licensed category. Ask how care plans adjust if mobility, nursing, or memory needs change over time. Read the family care guide → |
Public Google reviews
Fieldstone OrchardWest is generally praised for its clean, spacious environment and a staff that is described as caring and attentive to resident needs. Families appreciate the facility's proactive communication and safety measures, though some reviewers have noted that food quality could be improved.
Multiple reviewers consistently praise the staff for being loving, respectful, and attentive.
Families appreciate the facility's responsiveness and efforts to facilitate video calls.
Reviewers describe the facility as clean and spacious.
One reviewer calls the food wonderful, while another explicitly suggests the quality could be improved.
Residents are reported to enjoy daily exercise classes, bingo, and cornhole.
State licensing
5inspections
31deficiencies listed
1 deficiency reported
View official state report (opens in a new tab)
Next inspection scheduled on or after: 02/28/2027
Inspection, Testing and Maintenance of fire alarm and fire detection systemsIFC 907.8
The facility failed to provide documentation of the semi-annual fire alarm system inspection, testing, and maintenance within the past twelve months. (Corrected)
4 deficiencies reported
View official state report (opens in a new tab)
Initial inspection on 03/11/2025 was marked 'Disapproved'. A follow-up inspection on 04/10/2025 confirmed all listed violations were 'Corrected'.
Relocatable power taps and current tapsIFC 603.5 2021
Unfused 3-unit multi-plug adapter in use in Room 109 bathroom.
Fire safety, evacuation and lockdown plan contentsIFC 404.2 2021
Facility failed to provide documentation of fire drills for the Day and Noc shifts for the first quarter; drills for March/2024 to December/2024 were provided.
Equipment AccessIFC 509.2 2021
FACP Communicator box in the 1st Floor Janitors/Electrical Room was obstructed by combustible storage.
InstallationIFC 603.5.3 2021
Lift-assist bed cord in Room 201 was running through the bedroom door to the living room.
11 deficiencies reported
View official state report (opens in a new tab)
Inspection on 3/13/2024 resulted in Disapproved status; follow-up inspection on 4/22/2024 confirmed all violations corrected.
Abatement of Electrical HazardsIFC 604.1 2018
Employee Lounge refrigerator plugged into multi-plug adapter; coffee bar/vending area coffee appliances plugged into unfused power strip.
Testing and MaintenanceIFC 903.5 2009/2012/2015/2018
Facility unable to provide documentation of annual backflow test including forward flow test.
Ceiling ClearanceIFC 315.3.1 2018Corrected Mar 13, 2024
Maintenance Storage Room - failed to maintain storage 18 inches below the fire sprinkler head.
Hold-Open Devices and ClosersIFC 705.2.3 2018
Exercise room, business office, and library doors blocked open with objects; Room 219 door obstructed by wreath hanger.
Multiplug AdaptersIFC 604.4 2018
Multiple rooms and offices using unfused multiplug adapters, power strips, or extension cords incorrectly.
Working Space and ClearanceIFC 604.3 2018Corrected Mar 13, 2024
Electrical Room by Room 112 - combustible storage prevented access to electrical panel.
Portable Fire ExtinguishersIFC 906.2 2015/2018
Extinguisher near Room 202 undercharged; Laundry room extinguisher not inspected in Jan/Feb 2024.
Extension CordsIFC 604.5 2018
Room 205 - unfused multiplug adapter in use plugged into an extension cord.
ContentsIFC 404.2 2018
Facility was unable to provide documentation of the first quarter fire drills for the swing and night shifts.
Emergency Power for IlluminationIFC 1008.3 2018
Emergency lights in Room 219 and stairwell near Room 133 failed to illuminate.
Power SupplyIFC 604.4.2 2018
Relocatable power taps not connected directly to a permanently installed receptacle; improper use of multiplug adapters.
1 deficiency reported
View official state report (opens in a new tab)
A follow-up letter dated 05/02/2024 confirms compliance and correction of the deficiencies (Compliance Determination 40700).
Resident rightsWAC 388-78A-2660Corrected Apr 21, 2024
Facility failed to inform 3 of 3 residents in writing at least every 24 months of service items, activities, and rules of operation.
14 deficiencies reported
View official state report (opens in a new tab)
Follow-up inspection conducted on 04/27/2023 confirmed previous violations were corrected and facility is now approved.
Securing Compressed Gas ContainersIFC 5303.5.3 2018
Compressed tank in kitchen was unsecured.
Commercial Cooking SystemsIFC 904.12 2015, 2018
Kitchen hood suppression system blowoff cap dislodged and could not be replaced.
Power SupplyIFC 604.4.2 2018
Unfused multiplug adapter plugged into a multiplug block in Resident Room 111.
InitiationIFC 405.7 2018
Swing shift fire drills before 9 pm must include activation of an initiation device.
Multiplug AdaptersIFC 604.4 2018
Unfused multiplug adapters in use in Resident Rooms 205, 123, and 111.
Owner's ResponsibilityIFC 701.6 2018
Fire rated material in First Floor North Telecommunication Room has fallen out of rated construction.
Equipment Rooms - Storage in BuildingsIFC 315.3.3 2018
Combustible materials stored in First Floor Riser/Boiler Room and Fire Alarm Control Panel Room.
Smoke Detector SensitivityIFC 907.8.3 2012-2018
Unable to provide documentation of smoke detector sensitivity testing since 2018.
CleaningIFC 607.3.3 2018
Missing documentation of first semi-annual kitchen hood inspection/cleaning for the past 12 months.
Testing and MaintenanceIFC 903.5 2009-2018
Excessive particulate on kitchen sprinkler head; kitchen riser room obstructed; wire hanging on sprinkler pipe.
Door OperationIFC 705.2.4 2018
Cross corridor doors by Resident Room 120 do not latch; Receiving door does not close and latch.
Working Space and ClearanceIFC 604.3 2018
Items stored in front of electrical panels in Second Floor Sprinkler/Electrical Room.
Floor ClearanceIFC 906.9.3 2015, 2018
Fire extinguishers in maintenance office and elevator mechanical room were on the floor and unsecured.
FrequencyIFC 405.2 2015, 2018
Missing documentation of fire drills for all shifts during all four quarters (2022).
Neighborhood & resident support
Nearest hospital
Toppenish Community Hospital
20.1 mi · Toppenish, WA
FEMA hazard risk
Free resident advocacy
Washington State Long-Term Care Ombudsman Program
VA & dialysis access
Seattle VA Medical Center (VA Puget Sound Healthcare System)
105.4 mi · Seattle, WA · VA 4/5 ★
1.6 mi · 3/5 ★ · Home dialysis
Specialists within 15 mi
Environment & mobility
County demographics
Call & tour checklist
Check off questions as you call or tour. Your progress stays private in this browser.
Verification & public records
Verify licensing, ratings, and inspection reports directly with each official source.
EveryPlace is an independent research directory. Information is compiled from public Medicare.gov, state licensing, Google Places, and street-level imagery sources. Some summaries, suggested questions, and pricing notes are AI-generated or AI-assisted and may contain errors or omissions. We do not accept payment for placement. Confirm all details directly with the community and official sources. Research Policy.
Keep exploring