State Inspections

Source: WA Dept. of Social & Health Services

5total
10deficiencies
Jan 8, 2026Fire
CleanReport

Inspection conducted regarding complaint #207072 and follow-up to a December 30, 2025, annual inspection. The fire alarm system was confirmed operational, fire watch documentation was verified, and service reports for repairs were reviewed. No violations were noted.

Jan 8, 2026Fire

Both listed violations are marked as (Corrected) in the report. Next inspection scheduled on or after 12/31/2026.

Systems Out of ServiceIFC 901.7 2021

Fire alarm system had a trouble status for NAC circuits. Documentation indicated hardware failure and elevator recall/smoke detector testing inability. Fire watch required.

Compressed Gases - General - ScopeIFC 5301.1 2021

No designated storage areas for full and empty oxygen cylinders in the first-floor storage room.

Jul 11, 2025Inspection
CleanReport

The letter explicitly states that a full inspection was completed and no deficiencies were found.

Jan 13, 2025Fire

Inspection on 12/3/2024 resulted in a Disapproved status. A follow-up inspection on 1/13/2025 confirmed corrections for all listed items.

Relocatable power taps and current tapsIFC 603.5Corrected Jan 13, 2025

Unfused multi-plug adaptor in use in Room 319.

Application and UseIFC 603.5.2Corrected Jan 13, 2025

Power strip plugged into a power strip in Room 201.

Owner's ResponsibilityIFC 701.6Corrected Jan 13, 2025

Two penetrations in the third floor mechanical room ceiling; one penetration in the ceiling of Room 210 above the shower.

Hold-Open Devices and ClosersIFC 705.2.3Corrected Jan 13, 2025

Door to a room was propped open with a wedge.

Duct and Air Transfer OpeningsIFC 706.1Corrected Jan 13, 2025

Failed to provide documentation of correction for fire damper service report deficiency.

Sprinkler systemsIFC 903.5Corrected Jan 13, 2025

Missing documentation for annual sprinkler service, annual forward flow testing, and 5-year FDC hydro test; sprinkler heads on exterior canopy loaded with debris.

Inspection, Testing and MaintenanceIFC 907.8Corrected Jan 13, 2025

Failed to provide documentation for fire alarm sensitivity testing (last completed 2018).

Hazard Identification SignsIFC 5003.5Corrected Jan 13, 2025

Missing oxygen in use sign at the door to Room 209.

Jun 14, 2023Inspection
CleanReport

The Department completed a full inspection and found no deficiencies.

Contact

Get in Touch

Contact this facility directly and verify the details that matter most to your family.

References & Resources

EveryPlace is a research directory. Facility information is compiled from public sources — Medicare.gov, state licensing portals, Google Places, and publicly available street-level imagery. Listings do not constitute endorsement, recommendation, or advertisement, and we do not accept payment for placement. Families should verify all details directly with the facility and the original sources linked above before making any care decisions. See our Research Policy for our editorial standards, correction process, and image-removal policy.