Loading EveryPlace content…
Loading EveryPlace content…
State license
Active
WA DSHS
Google reviews
4.0/ 5
4 reviews
Size & payment
56 residents
Confirm pricing & payment
| Monthly cost | Not published | Ask for the full monthly cost, including care fees and one-time charges. |
|---|---|---|
| Payment options | Ask directly | Payment details are not confirmed in our records. Ask about private pay, long-term care insurance, veterans benefits, and Medicaid waivers. |
| Size & availability | 56 residents | We don't publish live openings. Ask about current availability, waitlist length, and move-in timing. |
| Care & support | Assisted living | Usually offers housing and help with everyday tasks, such as bathing and dressing. What to confirm about care levelsThis describes the licensed category. Ask how care plans adjust if mobility, nursing, or memory needs change over time. Read the family care guide → |
State licensing
4inspections
20deficiencies listed
12 deficiencies reported
View official state report (opens in a new tab)
Next inspection scheduled on or after 2027-02-28.
Owner's ResponsibilityIFC 701.6
Facility unable to provide documentation of fire-resistance rated wall inspections within the past 12 months.
Fire safety, evacuation and lockdown plan contentsIFC 404.2
Facility failed to provide documentation of fire drills being conducted for day, swing, and night shifts for all quarters in the past 12 months.
Power TestIFC 1031.10.2
Facility unable to provide documentation of 90-minute annual power test on battery back-up emergency lights and exit signs for the past 12 months.
Carbon Monoxide Detection - GeneralIFC 0915.1
Facility unable to provide documentation of monthly carbon monoxide alarm testing for the past 12 months.
Portable Fire Extinguishers - General RequirementsIFC 906.2
Fire extinguishers behind the Reception desk and in the Boiler Room were missing monthly inspections on the tag.
Working space and clearancesIFC 603.4
Combustible storage within 3' of electrical panel in Maintenance Room obstructing access.
Activation TestIFC 1032.10.1
Facility unable to provide documentation of 30-second monthly activation tests on battery back-up emergency lights and exit signs for the past 12 months.
MaintenanceIFC 1203.4
Facility unable to provide documentation of weekly inspections, monthly 30-minute full load testing, and annual service/maintenance on emergency generator.
Inspection and MaintenanceIFC 705.2
Facility unable to provide documentation of annual fire door inspections within the past 12 months.
Inspection, Testing and MaintenanceIFC 907.8
Facility unable to provide semi-annual fire alarm inspection documentation; FACP breaker (#28) lacked lock; pull stations blocked in Breakroom and near Room 104.
Hold-Open Devices and ClosersIFC 705.2.3
Fire rated doors in ED Office and Assistant ED Office had magnetic hold open devices not connected to fire alarm; doors in Rooms 132, 114, and 104 were propped open with door stoppers.
Testing and MaintenanceIFC 903.5
Facility unable to provide documentation of annual forward flow testing and quarterly fire sprinkler inspections for the 4th quarter within the past 12 months.
5 deficiencies reported
View official state report (opens in a new tab)
The report includes details of a kitchen fire that occurred on October 5, 2025. The inspection conducted on 10/29/2025 resulted in a 'Disapproved' status, but the subsequent inspection on 12/30/2025 lists the status as 'Approved' with all items marked as corrected.
Systems Out of ServiceIFC 901.7 2021
Facility failed to provide documentation of fire watch logs for the kitchen fire on October 5, 2025; failed to self-report fire alarm system out of service.
RecordsIFC 606.3.3.3 2021
Facility failed to provide documentation of scheduled cleaning logs completed by kitchen staff of appliances and cooking operations.
Grease ExtractorsIFC 606.3.2 2021
Facility failed to maintain the grease extractor on the MOTEX griddle appliance which was missing a lower grease extractor tray.
Restoring Systems to ServiceIFC 0901.7.6 2021
Facility failed to provide documentation of the UL300 commercial cooking system being restored to normal operations after the fire and failed to notify the AHJ.
Extinguishing System ServiceIFC 606.3.4 2021
Facility failed to provide documentation of the service to the UL300 commercial cooking system, testing and maintenance, and restoring the system to service after the fire on October 5, 2025.
1 deficiency reported
View official state report (opens in a new tab)
Includes complaint numbers 200166 and 199976. The fire suppression system was found to be back in compliance during the inspection.
Other requirementsWAC 388-78A-2040
Facility failed to assign staff to Fire Watch duty that had no other duties.
2 deficiencies reported
View official state report (opens in a new tab)
The report documents a complaint (#200166) regarding a fire alarm system that has been in trouble status periodically for two years due to fiber optic cable issues. Violations were marked as (Corrected) on the final inspection report.
Inspection, Testing and MaintenanceIFC 907.8 2021
The facility failed to maintain the fire alarm system inspection, testing, and maintenance; the system was in trouble status on 10/29/2025.
Systems Out of ServiceIFC 901.7 2021
The facility failed to notify the fire marshal of a fire alarm system outage observed on 10/29/2025. A fire watch was issued.
Neighborhood & resident support
Nearest hospital
Wenatchee Valley Hospital
1.2 mi · Wenatchee, WA
FEMA hazard risk
Free resident advocacy
Washington State Long-Term Care Ombudsman Program
VA & dialysis access
Seattle VA Medical Center (VA Puget Sound Healthcare System)
92.1 mi · Seattle, WA · VA 4/5 ★
0.2 mi · 2/5 ★
Specialists within 15 mi
Environment & mobility
County demographics
Call & tour checklist
Check off questions as you call or tour. Your progress stays private in this browser.
Verification & public records
Verify licensing, ratings, and inspection reports directly with each official source.
EveryPlace is an independent research directory. Information is compiled from public Medicare.gov, state licensing, Google Places, and street-level imagery sources. Some summaries, suggested questions, and pricing notes are AI-generated or AI-assisted and may contain errors or omissions. We do not accept payment for placement. Confirm all details directly with the community and official sources. Research Policy.
Keep exploring