State Inspection History

State Inspections

Source: WA Dept. of Social & Health Services

4total
20deficiencies
Apr 13, 2026Fire

Next inspection scheduled on or after 2027-02-28.

Fire safety, evacuation and lockdown plan contentsIFC 404.2

Facility failed to provide documentation of fire drills being conducted for day, swing, and night shifts for all quarters in the past 12 months.

Inspection and MaintenanceIFC 705.2

Facility unable to provide documentation of annual fire door inspections within the past 12 months.

Testing and MaintenanceIFC 903.5

Facility unable to provide documentation of annual forward flow testing and quarterly fire sprinkler inspections for the 4th quarter within the past 12 months.

Working space and clearancesIFC 603.4

Combustible storage within 3' of electrical panel in Maintenance Room obstructing access.

Carbon Monoxide Detection - GeneralIFC 0915.1

Facility unable to provide documentation of monthly carbon monoxide alarm testing for the past 12 months.

Power TestIFC 1031.10.2

Facility unable to provide documentation of 90-minute annual power test on battery back-up emergency lights and exit signs for the past 12 months.

Owner's ResponsibilityIFC 701.6

Facility unable to provide documentation of fire-resistance rated wall inspections within the past 12 months.

Hold-Open Devices and ClosersIFC 705.2.3

Fire rated doors in ED Office and Assistant ED Office had magnetic hold open devices not connected to fire alarm; doors in Rooms 132, 114, and 104 were propped open with door stoppers.

Inspection, Testing and MaintenanceIFC 907.8

Facility unable to provide semi-annual fire alarm inspection documentation; FACP breaker (#28) lacked lock; pull stations blocked in Breakroom and near Room 104.

Portable Fire Extinguishers - General RequirementsIFC 906.2

Fire extinguishers behind the Reception desk and in the Boiler Room were missing monthly inspections on the tag.

Activation TestIFC 1032.10.1

Facility unable to provide documentation of 30-second monthly activation tests on battery back-up emergency lights and exit signs for the past 12 months.

MaintenanceIFC 1203.4

Facility unable to provide documentation of weekly inspections, monthly 30-minute full load testing, and annual service/maintenance on emergency generator.

Dec 30, 2025Fire

The report includes details of a kitchen fire that occurred on October 5, 2025. The inspection conducted on 10/29/2025 resulted in a 'Disapproved' status, but the subsequent inspection on 12/30/2025 lists the status as 'Approved' with all items marked as corrected.

Systems Out of ServiceIFC 901.7 2021

Facility failed to provide documentation of fire watch logs for the kitchen fire on October 5, 2025; failed to self-report fire alarm system out of service.

Grease ExtractorsIFC 606.3.2 2021

Facility failed to maintain the grease extractor on the MOTEX griddle appliance which was missing a lower grease extractor tray.

Restoring Systems to ServiceIFC 0901.7.6 2021

Facility failed to provide documentation of the UL300 commercial cooking system being restored to normal operations after the fire and failed to notify the AHJ.

RecordsIFC 606.3.3.3 2021

Facility failed to provide documentation of scheduled cleaning logs completed by kitchen staff of appliances and cooking operations.

Extinguishing System ServiceIFC 606.3.4 2021

Facility failed to provide documentation of the service to the UL300 commercial cooking system, testing and maintenance, and restoring the system to service after the fire on October 5, 2025.

Nov 20, 2025Investigation

Includes complaint numbers 200166 and 199976. The fire suppression system was found to be back in compliance during the inspection.

Other requirementsWAC 388-78A-2040

Facility failed to assign staff to Fire Watch duty that had no other duties.

Nov 17, 2025Fire

The report documents a complaint (#200166) regarding a fire alarm system that has been in trouble status periodically for two years due to fiber optic cable issues. Violations were marked as (Corrected) on the final inspection report.

Systems Out of ServiceIFC 901.7 2021

The facility failed to notify the fire marshal of a fire alarm system outage observed on 10/29/2025. A fire watch was issued.

Inspection, Testing and MaintenanceIFC 907.8 2021

The facility failed to maintain the fire alarm system inspection, testing, and maintenance; the system was in trouble status on 10/29/2025.

Contact

Get in Touch

Contact this facility directly and verify the details that matter most to your family.

References & Resources

EveryPlace is a research directory. Facility information is compiled from public sources — Medicare.gov, state licensing portals, Google Places, and publicly available street-level imagery. Listings do not constitute endorsement, recommendation, or advertisement, and we do not accept payment for placement. Families should verify all details directly with the facility and the original sources linked above before making any care decisions. See our Research Policy for our editorial standards, correction process, and image-removal policy.